After 60 days of being unsupervised, the interval between successive A-Type Diagnostics will
increase to 24 hours. (Please note that after 60 days, if the radio is not supervised because
AlarmNet has not received a Contract or Request for Service for that radio, an additional
surcharge will be added to its monthly charge.)
Although the A-type Diagnostics contain important information for AlarmNet, as far as the
central station is concerned, receipt of the A-type Diagnostic message merely provides
confirmation that the newly installed account is being heard until it is assigned supervision by the
network.
Authentication –
no response
This feature is currently not available.
Authentication
Initialized
This feature is currently not available.
Authentication
Violation
This feature is currently not available.
Check 685 Printer This message is reported when an atypical system message is reported that may not normally be
passed on to the central station’s automation system. The “Check 685 Printer” message indicates
that the operator should refer to the printer output for an important message. Such messages
include:
A-Type diagnostics
F-Type diagnostics
Keyed-on subscriber
Repeating alarm suppressed
Redundant supervision warning
Multiple nodes down
2-Way radio internal tamper
Subscriber Command Failure
Unregistered subscriber
Central station Comm Fail
Database Update in Progress
Master/Host Alarm
Central Station Poll Timeout
Check-in Another name for an A-Type diagnostic. See “A-Type diagnostic”
Comm Fail See “Communications Failure Message”
Communications
Failure Alarm
Generated when a subscriber fails to check in with the network during its predetermined
supervision interval.
Communications
Failure Reminder
Communications Failure Reminders are sent every six hours for AlarmNet-A accounts, to remind
the central station that a subscriber continues to be in Communications Failure with the network.
For AlarmNet-M or AlarmNet-C subscribers, Comm Fail Reminders are not sent to the central
station. Instead, they are printed on the Weekly Status Report. This report shows the subscriber
number and the number of reminder messages the network would have generated. This means
that Communication Failure messages will only be sent ONLY ONCE for these radios.